CompTIA SK0-005 Practice Test 43
Question 420
A change board is planning a verified response to this server event: A colocation rack is left unlocked and vendor staff can touch network and backup equipment without approved escort or access records. For the Data center physical access enforcement issue, which response elements belong in the approved plan? Select TWO answers.
- Apply approved sanitization or cryptographic erase methods appropriate to media and classification, then retain evidence.
- A controlled simulated environmental warning reaches responders in time and temperature stays within equipment range.
- Enforce badges, role-based room or rack access, visitor logging and periodic access-review procedures.
- Review door events, camera footage, approved visitor roster, rack locks and access recertification.
- Assume a building lobby badge is sufficient authorization for every server rack.
Explanation
Correct Answer
C:Physical access can bypass many software controls; identity, escort and audit are needed at equipment boundaries. A successful outcome is: Every access to sensitive equipment has valid authorization and traceable access records.
D:These observations investigate the exact Data center physical access enforcement failure rather than unrelated components. The expected technical relationship is: Physical access can bypass many software controls; identity, escort and audit are needed at equipment boundaries.
Incorrect Answers
A:That option would apply approved sanitization or cryptographic erase methods appropriate to media and classification, then retain evidence, but it addresses a different concern. Physical access can bypass many software controls; identity, escort and audit are needed at equipment boundaries.
B:This statement concerns Environmental monitoring and suppression, a different Server+ technical control. It does not directly address the reported Data center physical access enforcement fault or prove its repair.
E:This is the unsafe shortcut in the Data center physical access enforcement scenario, not a justified remediation or diagnostic. Discriminate using: Review door events, camera footage, approved visitor roster, rack locks and access recertification.
Question 421
A server administrator is investigating a server issue involving environmental monitoring and suppression: A rack reports rising inlet temperatures after a CRAC failure, but operations waits for servers to shut down before escalating. The change must address the documented fault without creating unrelated risk. Which corrective action is most appropriate? Select ONE best answer.
- Enforce badges, role-based room or rack access, visitor logging and periodic access-review procedures.
- Ignore early cooling and leak alarms because the operating system remains responsive.
- Monitor temperature, humidity, water and fire risks with alarms and approved cooling or suppression response plans.
- Apply approved sanitization or cryptographic erase methods appropriate to media and classification, then retain evidence.
Explanation
Correct Answer
C:Physical environmental hazards can cause correlated service failures and must be detected before hardware shutdown.
Incorrect Answers
A:This statement concerns Data center physical access enforcement, a different Server+ technical control. It does not directly address the reported Environmental monitoring and suppression fault or prove its repair. For this incident, the relevant principle is: Physical environmental hazards can cause correlated service failures and must be detected before hardware shutdown. A targeted investigation checks: Inspect sensor placement, alert thresholds, cooling redundancy, water paths and fire-system maintenance records. The desired recovery condition is: A controlled simulated environmental warning reaches responders in time and temperature stays within equipment range.
B:This is the unsafe shortcut in the Environmental monitoring and suppression scenario, not a justified remediation or diagnostic. Physical environmental hazards can cause correlated service failures and must be detected before hardware shutdown.
D:That option would apply approved sanitization or cryptographic erase methods appropriate to media and classification, then retain evidence, but it addresses a different concern. Physical environmental hazards can cause correlated service failures and must be detected before hardware shutdown.
Question 422
While reviewing the CompTIA Server+ administration incident, a technician learns: A rack reports rising inlet temperatures after a CRAC failure, but operations waits for servers to shut down before escalating. Which principle most directly explains how to address the described issue safely? Select ONE best answer.
- Physical environmental hazards can cause correlated service failures and must be detected before hardware shutdown.
- Risk-based remediation combines technical severity and local exposure; score alone does not establish operational priority.
- Patch management balances exposure reduction with service continuity using tested change windows and exception handling.
- Backup resilience requires separation of failure and credential domains; multiple files on one failure domain are not independent copies.
Explanation
Correct Answer
A:Collect evidence first: Inspect sensor placement, alert thresholds, cooling redundancy, water paths and fire-system maintenance records.
Incorrect Answers
B:This statement concerns Vulnerability scanning and prioritization, a different Server+ technical control. It does not directly address the reported Environmental monitoring and suppression fault or prove its repair. For this incident, the relevant principle is: Physical environmental hazards can cause correlated service failures and must be detected before hardware shutdown. A targeted investigation checks: Inspect sensor placement, alert thresholds, cooling redundancy, water paths and fire-system maintenance records. The desired recovery condition is: A controlled simulated environmental warning reaches responders in time and temperature stays within equipment range.
C:This statement concerns Patching with staged rollback, a different Server+ technical control. It does not directly address the reported Environmental monitoring and suppression fault or prove its repair. For this incident, the relevant principle is: Physical environmental hazards can cause correlated service failures and must be detected before hardware shutdown. A targeted investigation checks: Inspect sensor placement, alert thresholds, cooling redundancy, water paths and fire-system maintenance records. The desired recovery condition is: A controlled simulated environmental warning reaches responders in time and temperature stays within equipment range.
D:This statement concerns Immutable and offsite backup strategy, a different Server+ technical control. It does not directly address the reported Environmental monitoring and suppression fault or prove its repair. For this incident, the relevant principle is: Physical environmental hazards can cause correlated service failures and must be detected before hardware shutdown. A targeted investigation checks: Inspect sensor placement, alert thresholds, cooling redundancy, water paths and fire-system maintenance records. The desired recovery condition is: A controlled simulated environmental warning reaches responders in time and temperature stays within equipment range.
Question 423
Before a server change is approved, the on-call engineer receives this incident report: A rack reports rising inlet temperatures after a CRAC failure, but operations waits for servers to shut down before escalating. Which evidence would most directly establish the stated root-cause hypothesis? Select ONE best answer.
- Review door events, camera footage, approved visitor roster, rack locks and access recertification.
- Inspect sensor placement, alert thresholds, cooling redundancy, water paths and fire-system maintenance records.
- Ignore early cooling and leak alarms because the operating system remains responsive.
- Check asset exposure, affected software versions, exploit availability, scan confidence and compensating controls.
Explanation
Correct Answer
B:The expected technical relationship is: Physical environmental hazards can cause correlated service failures and must be detected before hardware shutdown.
Incorrect Answers
A:For this incident, the relevant principle is: Physical environmental hazards can cause correlated service failures and must be detected before hardware shutdown. A targeted investigation checks: Inspect sensor placement, alert thresholds, cooling redundancy, water paths and fire-system maintenance records.
C:This is the unsafe shortcut in the Environmental monitoring and suppression scenario, not a justified remediation or diagnostic. Discriminate using: Inspect sensor placement, alert thresholds, cooling redundancy, water paths and fire-system maintenance records.
D:For this incident, the relevant principle is: Physical environmental hazards can cause correlated service failures and must be detected before hardware shutdown.
Question 424
After the team implements a targeted remediation for Environmental monitoring and suppression, the original incident was: A rack reports rising inlet temperatures after a CRAC failure, but operations waits for servers to shut down before escalating. Which acceptance criterion would best demonstrate a durable and safe resolution? Select ONE best answer.
- Decommissioned media has verifiable sanitization or destruction evidence matching policy.
- A rehearsal restores end-to-end service within RTO and loses no more than allowed by RPO.
- Patches deploy without unacceptable outage and vulnerability scans verify the intended fixed version.
- A controlled simulated environmental warning reaches responders in time and temperature stays within equipment range.
Explanation
Correct Answer
D:Physical environmental hazards can cause correlated service failures and must be detected before hardware shutdown.
Incorrect Answers
A:This statement concerns Media sanitization by classification, a different Server+ technical control. It does not directly address the reported Environmental monitoring and suppression fault or prove its repair. For this incident, the relevant principle is: Physical environmental hazards can cause correlated service failures and must be detected before hardware shutdown. A targeted investigation checks: Inspect sensor placement, alert thresholds, cooling redundancy, water paths and fire-system maintenance records. The desired recovery condition is: A controlled simulated environmental warning reaches responders in time and temperature stays within equipment range.
B:This statement concerns RPO and RTO-driven disaster recovery, a different Server+ technical control. It does not directly address the reported Environmental monitoring and suppression fault or prove its repair. For this incident, the relevant principle is: Physical environmental hazards can cause correlated service failures and must be detected before hardware shutdown. A targeted investigation checks: Inspect sensor placement, alert thresholds, cooling redundancy, water paths and fire-system maintenance records. The desired recovery condition is: A controlled simulated environmental warning reaches responders in time and temperature stays within equipment range.
C:This statement concerns Patching with staged rollback, a different Server+ technical control. It does not directly address the reported Environmental monitoring and suppression fault or prove its repair.
Question 425
A change board is planning a verified response to this server event: A rack reports rising inlet temperatures after a CRAC failure, but operations waits for servers to shut down before escalating. For the Environmental monitoring and suppression issue, which response elements belong in the approved plan? Select ONE best answer.
- Prioritize verified vulnerabilities by exploitability, exposure and business impact; apply supported remediations with evidence.
- Capture denied flows, review service dependency map, evaluate host firewall rule precedence and test expected ports.
- Monitor temperature, humidity, water and fire risks with alarms and approved cooling or suppression response plans. Then validate the change by confirming: A controlled simulated environmental warning reaches responders in time and temperature stays within equipment range.
- Ignore early cooling and leak alarms because the operating system remains responsive.
Explanation
Correct Answer
C:Physical environmental hazards can cause correlated service failures and must be detected before hardware shutdown. Before modifying systems, gather: Inspect sensor placement, alert thresholds, cooling redundancy, water paths and fire-system maintenance records.
Incorrect Answers
A:This statement concerns Vulnerability scanning and prioritization, a different Server+ technical control. It does not directly address the reported Environmental monitoring and suppression fault or prove its repair.
B:This statement concerns Host firewall and east-west filtering, a different Server+ technical control. It does not directly address the reported Environmental monitoring and suppression fault or prove its repair. For this incident, the relevant principle is: Physical environmental hazards can cause correlated service failures and must be detected before hardware shutdown. A targeted investigation checks: Inspect sensor placement, alert thresholds, cooling redundancy, water paths and fire-system maintenance records. The desired recovery condition is: A controlled simulated environmental warning reaches responders in time and temperature stays within equipment range.
D:This is the unsafe shortcut in the Environmental monitoring and suppression scenario, not a justified remediation or diagnostic. Incident: A rack reports rising inlet temperatures after a CRAC failure, but operations waits for servers to shut down before escalating.
Question 426
A server administrator is investigating a server issue involving environmental monitoring and suppression: A small data closet lacks leak sensors or appropriate fire suppression and places a water pipe above an unprotected UPS. The change must address the documented fault without creating unrelated risk. Which corrective action is most appropriate? Select ONE best answer.
- Classify sensitive records and enforce least-necessary access, approved retention and controlled export or redaction.
- Restore supported TLS with a valid certificate chain, correct names and trusted issuers; keep client validation enabled.
- Monitor temperature, humidity, water and fire risks with alarms and approved cooling or suppression response plans.
- Ignore early cooling and leak alarms because the operating system remains responsive.
Explanation
Correct Answer
C:Physical environmental hazards can cause correlated service failures and must be detected before hardware shutdown.
Incorrect Answers
A:This statement concerns Data classification and retention controls, a different Server+ technical control. It does not directly address the reported Environmental monitoring and suppression fault or prove its repair. For this incident, the relevant principle is: Physical environmental hazards can cause correlated service failures and must be detected before hardware shutdown. A targeted investigation checks: Inspect sensor placement, alert thresholds, cooling redundancy, water paths and fire-system maintenance records. The desired recovery condition is: A controlled simulated environmental warning reaches responders in time and temperature stays within equipment range.
B:This statement concerns TLS certificate chain and secure transport, a different Server+ technical control. It does not directly address the reported Environmental monitoring and suppression fault or prove its repair. For this incident, the relevant principle is: Physical environmental hazards can cause correlated service failures and must be detected before hardware shutdown. A targeted investigation checks: Inspect sensor placement, alert thresholds, cooling redundancy, water paths and fire-system maintenance records. The desired recovery condition is: A controlled simulated environmental warning reaches responders in time and temperature stays within equipment range.
D:This is the unsafe shortcut in the Environmental monitoring and suppression scenario, not a justified remediation or diagnostic. Incident: A small data closet lacks leak sensors or appropriate fire suppression and places a water pipe above an unprotected UPS.
Question 427
While reviewing the CompTIA Server+ administration incident, a technician learns: A small data closet lacks leak sensors or appropriate fire suppression and places a water pipe above an unprotected UPS. Which principle most directly explains how to address the described issue safely? Select ONE best answer.
- Data-protection controls should follow sensitivity and approved retention; a technically reachable storage bucket is not automatically an authorized destination.
- File permissions do not protect stolen offline media; encryption's value depends on safeguarding keys and recoverability.
- Physical environmental hazards can cause correlated service failures and must be detected before hardware shutdown.
- Encryption in transit needs authenticated peers, valid trust chains and modern protocol settings, not merely an encrypted port.
Explanation
Correct Answer
C:Collect evidence first: Inspect sensor placement, alert thresholds, cooling redundancy, water paths and fire-system maintenance records.
Incorrect Answers
A:This statement concerns Data classification and retention controls, a different Server+ technical control. It does not directly address the reported Environmental monitoring and suppression fault or prove its repair.
B:This statement concerns Encryption at rest and key lifecycle, a different Server+ technical control. It does not directly address the reported Environmental monitoring and suppression fault or prove its repair. For this incident, the relevant principle is: Physical environmental hazards can cause correlated service failures and must be detected before hardware shutdown. A targeted investigation checks: Inspect sensor placement, alert thresholds, cooling redundancy, water paths and fire-system maintenance records. The desired recovery condition is: A controlled simulated environmental warning reaches responders in time and temperature stays within equipment range.
D:This statement concerns TLS certificate chain and secure transport, a different Server+ technical control. It does not directly address the reported Environmental monitoring and suppression fault or prove its repair.
Question 428
Before a server change is approved, the on-call engineer receives this incident report: A small data closet lacks leak sensors or appropriate fire suppression and places a water pipe above an unprotected UPS. Which evidence would most directly establish the stated root-cause hypothesis? Select ONE best answer.
- Inspect sensor placement, alert thresholds, cooling redundancy, water paths and fire-system maintenance records.
- Inspect storage encryption status, backup-media handling, key custody, access logs and tested recovery access.
- Ignore early cooling and leak alarms because the operating system remains responsive.
- Inspect authentication policy, MFA enrollment, privileged-session records and emergency account use.
Explanation
Correct Answer
A:The expected technical relationship is: Physical environmental hazards can cause correlated service failures and must be detected before hardware shutdown.
Incorrect Answers
B:For this incident, the relevant principle is: Physical environmental hazards can cause correlated service failures and must be detected before hardware shutdown.
C:Physical environmental hazards can cause correlated service failures and must be detected before hardware shutdown.
D:For this incident, the relevant principle is: Physical environmental hazards can cause correlated service failures and must be detected before hardware shutdown. This statement concerns MFA and just-in-time administration, a different Server+ technical control.
Question 429
After the team implements a targeted remediation for Environmental monitoring and suppression, the original incident was: A small data closet lacks leak sensors or appropriate fire suppression and places a water pipe above an unprotected UPS. Which acceptance criterion would best demonstrate a durable and safe resolution? Select ONE best answer.
- A controlled simulated environmental warning reaches responders in time and temperature stays within equipment range.
- Users complete critical transactions in the alternate site, and a rehearsed failback restores a consistent primary.
- Every access to sensitive equipment has valid authorization and traceable access records.
- Clients establish mutually appropriate authenticated encrypted connections with verification enabled.
Explanation
Correct Answer
A:Physical environmental hazards can cause correlated service failures and must be detected before hardware shutdown.
Incorrect Answers
B:This statement concerns Site failover dependencies and failback, a different Server+ technical control. It does not directly address the reported Environmental monitoring and suppression fault or prove its repair. For this incident, the relevant principle is: Physical environmental hazards can cause correlated service failures and must be detected before hardware shutdown. A targeted investigation checks: Inspect sensor placement, alert thresholds, cooling redundancy, water paths and fire-system maintenance records. The desired recovery condition is: A controlled simulated environmental warning reaches responders in time and temperature stays within equipment range.
C:This statement concerns Data center physical access enforcement, a different Server+ technical control. It does not directly address the reported Environmental monitoring and suppression fault or prove its repair. For this incident, the relevant principle is: Physical environmental hazards can cause correlated service failures and must be detected before hardware shutdown. A targeted investigation checks: Inspect sensor placement, alert thresholds, cooling redundancy, water paths and fire-system maintenance records. The desired recovery condition is: A controlled simulated environmental warning reaches responders in time and temperature stays within equipment range.
D:This statement concerns TLS certificate chain and secure transport, a different Server+ technical control. It does not directly address the reported Environmental monitoring and suppression fault or prove its repair. For this incident, the relevant principle is: Physical environmental hazards can cause correlated service failures and must be detected before hardware shutdown.
Question 430
A change board is planning a verified response to this server event: A small data closet lacks leak sensors or appropriate fire suppression and places a water pipe above an unprotected UPS. For the Environmental monitoring and suppression issue, which response elements belong in the approved plan? Select TWO answers.
- Enable appropriate data-at-rest encryption with separated, access-controlled key storage, recovery procedures and rotation policy.
- Ignore early cooling and leak alarms because the operating system remains responsive.
- Inspect sensor placement, alert thresholds, cooling redundancy, water paths and fire-system maintenance records.
- Monitor temperature, humidity, water and fire risks with alarms and approved cooling or suppression response plans.
- Every access to sensitive equipment has valid authorization and traceable access records.
Explanation
Correct Answer
C:The expected technical relationship is: Physical environmental hazards can cause correlated service failures and must be detected before hardware shutdown. These observations investigate the exact Environmental monitoring and suppression failure rather than unrelated components.
D:Physical environmental hazards can cause correlated service failures and must be detected before hardware shutdown. Before rollout, confirm the problem with: Inspect sensor placement, alert thresholds, cooling redundancy, water paths and fire-system maintenance records.
Incorrect Answers
A:For this incident, the relevant principle is: Physical environmental hazards can cause correlated service failures and must be detected before hardware shutdown. This statement concerns Encryption at rest and key lifecycle, a different Server+ technical control.
B:Discriminate using: Inspect sensor placement, alert thresholds, cooling redundancy, water paths and fire-system maintenance records.
E:For this incident, the relevant principle is: Physical environmental hazards can cause correlated service failures and must be detected before hardware shutdown. This statement concerns Data center physical access enforcement, a different Server+ technical control.